JobVolt
Table 310.16 · 240.4(D)

How Many Amps Can 14 AWG Copper Wire Handle?

Verified against NEC 2023, checked against the 2026 edition · Last checked August 19, 2026

14 AWG copper wire carries 15 A at 60°C, 20 A at 75°C and 25 A at 90°C · Table 310.16. Which column applies depends on the termination rating · 110.14(C). NM-B cable always uses the 60°C column · 334.80. No matter the column, the breaker on 14 AWG copper tops out at 15 A · 240.4(D).

Common on this size: lighting and 15 A receptacle circuits.

14 AWG copper allowable ampacity by termination column. Not more than three current-carrying conductors, 86°F ambient. Same values in NEC 2023 and 2026.
Column · insulation examplesAmpacityBasis
60°C · TW, UF15 ATable 310.16
75°C · THW, THWN, XHHW wet, USE20 ATable 310.16
90°C · THHN, THWN-2, XHHW-225 ATable 310.16
Maximum breaker15 A240.4(D)

THHW and XHHW are 90°C only in dry and damp locations; wet locations put them in the 75°C column. XHHW-2 and THWN-2 hold 90°C wet or dry · Table 310.4(1).

Adjustment factors for more than three current-carrying conductors in one raceway or cable, applied to the 14 AWG values above · Table 310.15(C)(1).
Current-carrying conductorsPercent of table ampacity
4 to 680%
7 to 970%
10 to 2050%
21 to 3045%
31 to 4040%
41 and more35%

Ambient above 86°F applies a further correction from the band table of 310.15(B)(1). The free wire size calculator applies both automatically.

Derate it in seconds, offline.

The JobVolt app applies ambient correction, conductor adjustment and termination limits to 14 AWG copper with every step cited, then exports inspector-ready PDF submittals.

Download on the App StoreGet it on Google Play

Common questions

How many amps can 14 gauge copper wire handle?
15 A at 60°C terminations, 20 A at 75°C and 25 A at 90°C, per NEC Table 310.16 with no more than three current-carrying conductors at 86°F ambient. The overcurrent device still caps at 15 A · 240.4(D).
What size breaker goes on 14 AWG copper?
15 A is the maximum · 240.4(D). Larger breakers are not permitted on 14 AWG copper outside specific rules like motor circuits · 240.4(G).
Why does the chart say 25 A for 14 AWG copper but the breaker only 15 A?
25 A is the 90°C table ampacity, the starting point for derating. The small-conductor rule caps the overcurrent device separately · 240.4(D). Both are true at once.
Does conduit fill change the ampacity of 14 AWG copper?
Four or more current-carrying conductors in one raceway derate the table value · 310.15(C)(1). At 4 to 6 conductors, 14 AWG copper starts from 80% of the 90°C cell: 20 A before any further correction. Heat above 86°F derates it further · 310.15(B)(1).