Table 310.16 · NEC reference

NEC Table 310.16 Ampacity Chart

Allowable ampacities for insulated copper and aluminum conductors, 14 AWG through 1000 kcmil, from NEC Table 310.16. The values are identical in the 2023 and 2026 editions carried by the JobVolt dataset.

Need a sized answer, not a lookup? Open the free Wire Size Calculator. It reads this same dataset and shows every step.

NEC Table 310.16, allowable ampacities in amperes for copper conductors rated 60°C, 75°C and 90°C, not more than three current-carrying conductors in a raceway, 30°C (86°F) ambient temperature. NEC 2023 and 2026 editions.
Size60°C75°C90°C
14 AWG152025
12 AWG202530
10 AWG303540
8 AWG405055
6 AWG556575
4 AWG708595
3 AWG85100115
2 AWG95115130
1 AWG110130145
1/0 AWG125150170
2/0 AWG145175195
3/0 AWG165200225
4/0 AWG195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil350420475
700 kcmil385460520
750 kcmil400475535
1000 kcmil455545615

Ampacities from NEC Table 310.16, 30°C ambient basis, copper. Apply correction and adjustment factors before use · 310.15(B)(1), 310.15(C)(1).

NEC Table 310.16, allowable ampacities in amperes for aluminum conductors rated 60°C, 75°C and 90°C, not more than three current-carrying conductors in a raceway, 30°C (86°F) ambient temperature. NEC 2023 and 2026 editions.
Size60°C75°C90°C
12 AWG152025
10 AWG253035
8 AWG354045
6 AWG405055
4 AWG556575
3 AWG657585
2 AWG7590100
1 AWG85100115
1/0 AWG100120135
2/0 AWG115135150
3/0 AWG130155175
4/0 AWG150180205
250 kcmil170205230
300 kcmil195230260
350 kcmil210250280
400 kcmil225270305
500 kcmil260310350
600 kcmil285340385
700 kcmil315375425
750 kcmil320385435
1000 kcmil375445500

Ampacities from NEC Table 310.16, 30°C ambient basis, aluminum. Apply correction and adjustment factors before use · 310.15(B)(1), 310.15(C)(1).

Maximum overcurrent protection for small conductors · 240.4(D)
ConductorCopperAluminum
14 AWG15 A
12 AWG20 A15 A
10 AWG30 A25 A

Overcurrent protection caps for small conductors per 240.4(D). They apply regardless of the ampacity shown in Table 310.16.

How to read Table 310.16

Find your conductor material and size, then read the column that matches the insulation temperature rating for the location, wet or dry. THHN, the everyday raceway conductor, reads from the 90°C column. The table assumes not more than three current-carrying conductors in a raceway or cable and a 30°C (86°F) ambient. Change either condition and the printed number no longer applies as-is.

The column you can actually use

The insulation column and the column you may load are different questions. Terminations govern. Unless the equipment is marked otherwise, circuits rated 100 A or less are sized from the 60°C column, and larger circuits from the 75°C column · 110.14(C). The 90°C column still earns its keep: it is the starting point for derating, so a THHN conductor survives correction factors that would sink a TW conductor of the same size.

Corrections that change the number

For ambient temperatures other than 30°C, multiply by the correction factor · 310.15(B)(1). For more than three current-carrying conductors in a raceway or cable, apply the adjustment factor · 310.15(C)(1). After all of that, small conductors hit a hard stop: 15 A for 14 AWG copper, 20 A for 12 AWG copper and 30 A for 10 AWG copper, with the aluminum caps shown above · 240.4(D). The free wire size calculator runs the whole chain and shows which limit governed.