JobVolt
Table 250.66 · NEC reference

NEC Table 250.66 GEC Sizing

Grounding electrode conductor size from NEC Table 250.66, listed for every standard service-entrance conductor size in copper and aluminum. The GEC connects the grounded service conductor to the grounding electrode system, and it is sized from the service conductors, not the overcurrent device.

NEC Table 250.66, grounding electrode conductor size by the largest ungrounded copper service-entrance conductor, listed per standard conductor size
Service CuGEC copperGEC aluminum
14 AWG8 AWG6 AWG
12 AWG8 AWG6 AWG
10 AWG8 AWG6 AWG
8 AWG8 AWG6 AWG
6 AWG8 AWG6 AWG
4 AWG8 AWG6 AWG
3 AWG8 AWG6 AWG
2 AWG8 AWG6 AWG
1 AWG6 AWG4 AWG
1/0 AWG6 AWG4 AWG
2/0 AWG4 AWG2 AWG
3/0 AWG4 AWG2 AWG
4/0 AWG2 AWG1/0 AWG
250 kcmil2 AWG1/0 AWG
300 kcmil2 AWG1/0 AWG
350 kcmil2 AWG1/0 AWG
400 kcmil1/0 AWG3/0 AWG
500 kcmil1/0 AWG3/0 AWG
600 kcmil1/0 AWG3/0 AWG
700 kcmil2/0 AWG4/0 AWG
750 kcmil2/0 AWG4/0 AWG
1000 kcmil2/0 AWG4/0 AWG

NEC Table 250.66. Grounding electrode conductor by the largest ungrounded service-entrance conductor, copper service, sizes in AWG or kcmil. The printed table states ranges; for parallel sets, size from the equivalent area of the set. Electrode-type caps of 250.66(A) through (C) are not applied here.

NEC Table 250.66, grounding electrode conductor size by the largest ungrounded aluminum service-entrance conductor, listed per standard conductor size
Service AlGEC copperGEC aluminum
12 AWG8 AWG6 AWG
10 AWG8 AWG6 AWG
8 AWG8 AWG6 AWG
6 AWG8 AWG6 AWG
4 AWG8 AWG6 AWG
3 AWG8 AWG6 AWG
2 AWG8 AWG6 AWG
1 AWG8 AWG6 AWG
1/0 AWG8 AWG6 AWG
2/0 AWG6 AWG4 AWG
3/0 AWG6 AWG4 AWG
4/0 AWG4 AWG2 AWG
250 kcmil4 AWG2 AWG
300 kcmil2 AWG1/0 AWG
350 kcmil2 AWG1/0 AWG
400 kcmil2 AWG1/0 AWG
500 kcmil2 AWG1/0 AWG
600 kcmil1/0 AWG3/0 AWG
700 kcmil1/0 AWG3/0 AWG
750 kcmil1/0 AWG3/0 AWG
1000 kcmil2/0 AWG4/0 AWG

NEC Table 250.66. Grounding electrode conductor by the largest ungrounded service-entrance conductor, aluminum service, sizes in AWG or kcmil. The printed table states ranges; for parallel sets, size from the equivalent area of the set. Electrode-type caps of 250.66(A) through (C) are not applied here.

How to use this table

Find the largest ungrounded service-entrance conductor in the left column and read the required GEC in copper or aluminum. For parallel service conductors, the printed table works on the equivalent area of the set: add the circular mils of one phase's parallel conductors together and size from that total. The lookup above lists each standard size individually, which is how the JobVolt grounding engine reads the same table.

The electrode caps

Certain electrodes cannot use more conductor than they can deliver. A connection that serves only a rod, pipe or plate electrode never needs a GEC larger than 6 AWG copper or 4 AWG aluminum · 250.66(A). A connection serving only a concrete-encased electrode never needs more than 4 AWG copper · 250.66(B). A ground ring connection never needs to be larger than the ring conductor itself · 250.66(C). An aluminum GEC also cannot terminate within 18 inches of the earth · 250.64(A).

GEC is not EGC

The grounding electrode conductor and the equipment grounding conductor answer different questions. The EGC runs with the circuit conductors and is sized from the overcurrent device per Table 250.122. The JobVolt app's grounding calculator sizes both, applies the electrode caps and the 250.122(B) upsizing rule, and cites each step.