NEC Motor Full-Load Current Tables

Motor full-load currents from NEC Table 430.248 for single-phase motors and Table 430.250 for three-phase AC squirrel-cage induction motors. Wound-rotor and synchronous motors use different table columns not shown here.

NEC Table 430.248, full-load current in amperes, single-phase alternating-current motors, 1/6 through 10 hp
hp115 V200 V208 V230 V
1/64.42.52.42.2
1/45.83.33.22.9
1/37.24.143.6
1/29.85.65.44.9
3/413.87.97.66.9
1169.28.88
1.52011.51110
22413.813.212
33419.618.717
55632.230.828
7.580464440
1010057.55550

NEC Table 430.248. Full-load current in amperes. Wire and OCPD are sized from these table values, not the nameplate · 430.6(A).

NEC Table 430.250, full-load current in amperes, three-phase squirrel-cage induction motors, 1/2 through 200 hp
hp200 V208 V230 V460 V575 V
1/22.52.42.21.10.9
3/43.73.53.21.61.3
14.84.64.22.11.7
1.56.96.6632.4
27.87.56.83.42.7
31110.69.64.83.9
517.516.715.27.66.1
7.525.324.222119
1032.230.8281411
1548.346.2422117
2062.159.4542722
2578.274.8683427
309288804032
401201141045241
501501431306552
601771691547762
752212111929677
10028527324812499
125359343312156125
150414396360180144
200552528480240192

NEC Table 430.250. Full-load current in amperes. Wire and OCPD are sized from these table values, not the nameplate · 430.6(A).

Maximum rating of the branch-circuit short-circuit and ground-fault protective device, in percent of full-load current · 430.52(C)(1)
Protection typeMax % of FLC
Inverse-time breaker250%
Dual-element fuse175%
Non-time-delay fuse300%
Instantaneous trip800%

Percentages per 430.52(C)(1) for the protection types the JobVolt motor calculator covers. Where the computed value does not match a standard rating, the next standard size up is permitted · 430.52(C)(1) Exc. 1. Instantaneous trip: listed combination controllers only · 430.52(C)(3).

Table current, not nameplate

The code is explicit: conductor ampacity and branch-circuit protection for a motor are sized from these table values, not from the current stamped on the nameplate · 430.6(A). The nameplate amps matter for one thing only, overload protection. That split is the most common motor-sizing mistake in the field.

The three sizes every motor needs

From the table FLC, branch-circuit conductors must carry at least 125% · 430.22. The short-circuit and ground-fault device is capped by the percentages above · 430.52(C)(1), rounding up to the next standard size where permitted · 430.52(C)(1) Exc. 1. Overload protection comes from the nameplate instead: trip at 125% of nameplate amps for motors with a service factor of 1.15 or more, or 115% otherwise · 430.32(A)(1). Three different numbers, three different code sections, all from one motor.