JobVolt
Ch. 9 Tables 1, 4, 5 · NEC reference

NEC Conduit Fill Chart

Everything conduit fill runs on, in one place: the fill percentages of Chapter 9 Table 1, a computed chart of maximum THHN/THWN-2 conductors in EMT, the raceway internal areas of Table 4 for seven raceway types, and the conductor areas of Table 5.

Need a sized answer, not a lookup? Open the free Conduit Fill Calculator. It reads this same dataset and shows every step.

Maximum raceway fill in percent of internal area · Ch. 9 Table 1
Conductors in the racewayMaximum fill
One conductor53%
Two conductors31%
Three or more conductors40%
Nipple, 24 in or shorter, any count60%

Fill limits per NEC Ch. 9 Table 1. Nipples not exceeding 24 inches may be filled to 60% · Ch. 9 Note 4.

Maximum number of THHN / THWN-2 conductors in EMT by trade size, all conductors the same size · Ch. 9 Tables 1, 4, 5
Conductor1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"3-1/2"4"
14 AWG1222356184138200200200200
12 AWG916264561101176200200200
10 AWG51016283863111167200200
8 AWG3691622366496126161
6 AWG247121626466991116
4 AWG1247101628435671
3 AWG113681324364760
2 AWG113571120304051
1 AWG11145815222937
1/0 AWG11134712192532
2/0 AWG1123610162026
3/0 AWG111358131722
4/0 AWG111247111418
250 kcmil1113691115
300 kcmil1113571013
350 kcmil111246911
400 kcmil11146810
500 kcmil1113568
600 kcmil1112457
700 kcmil1112346
750 kcmil111345
1000 kcmil111234

Counts computed from the EMT areas of Ch. 9 Table 4 and the conductor areas of Ch. 9 Table 5, with the fill limits of Ch. 9 Table 1 and the rounding allowance of Ch. 9 Note 7, exactly as the JobVolt conduit fill calculator checks a run. For mixed conductor sizes or types, fill must be computed by area, not read from this chart.

Raceway internal cross-section area in square inches, 100% of area · Ch. 9 Table 4
Trade sizeEMTENTFMCIMCRMC (rigid)PVC Sch 40PVC Sch 80
1/2"0.3040.2850.3170.3420.3140.2850.217
3/4"0.5330.5080.5330.5860.5490.5080.409
1"0.8640.8320.8170.9590.8870.8320.688
1-1/4"1.4961.4531.2771.6471.5261.4531.237
1-1/2"2.0361.9861.8582.2252.0711.9861.711
2"3.3563.2913.2693.6303.4083.2912.874
2-1/2"5.8584.9095.1354.8664.6954.119
3"8.8467.0697.9227.4997.2686.442
3-1/2"11.5459.62110.58410.0109.7378.688
4"14.75312.56613.63112.88212.55411.258
5"20.21219.76117.855
6"29.15828.56725.598

Total internal areas per NEC Ch. 9 Table 4. Multiply by the Table 1 percentage that matches your conductor count to get the allowable fill area. A dash means the raceway is not made in that trade size.

Approximate conductor cross-section area in square inches, by insulation type · Ch. 9 Table 5
ConductorTHHN / THWN-2XHHW-2 / XHHTHW / THHW / THW-2TW
14 AWG0.00970.01390.01390.0139
12 AWG0.01330.01810.01810.0181
10 AWG0.02110.02430.02430.0243
8 AWG0.03660.04370.04370.0437
6 AWG0.05070.05900.07260.0726
4 AWG0.08240.08140.09730.0973
3 AWG0.09730.09620.11340.1134
2 AWG0.11580.11460.13330.1333
1 AWG0.15620.15340.19010.1901
1/0 AWG0.18550.18250.2223
2/0 AWG0.22230.21900.2624
3/0 AWG0.26790.26420.3117
4/0 AWG0.32370.31970.3718
250 kcmil0.39700.39040.4596
300 kcmil0.46080.45360.5281
350 kcmil0.52420.51660.5958
400 kcmil0.58630.57820.6619
500 kcmil0.70730.69840.7901
600 kcmil0.86760.87090.9729
700 kcmil0.98870.99231.1010
750 kcmil1.04961.05321.1652
1000 kcmil1.34781.35191.4784

Approximate areas of insulated conductors per NEC Ch. 9 Table 5. Sum the areas of every conductor in the raceway and compare against the allowable fill area from Tables 1 and 4.

How conduit fill works

Fill is an area problem. Each insulated conductor occupies the area listed in Chapter 9 Table 5. The raceway offers the internal area listed in Chapter 9 Table 4. Table 1 says how much of that area you may use: 53% for one conductor, 31% for two, 40% for three or more, and 60% for a nipple 24 inches or shorter. If the summed conductor area fits inside the allowed area, the run complies.

Reading the EMT chart

The chart answers the everyday question directly: how many conductors of one size fit in a given EMT trade size. It applies the Note 7 allowance, which lets the count round up when the division lands at 0.8 or higher past the whole number. The moment you mix sizes or insulation types in one raceway, the chart no longer applies and the calculation goes back to areas. The free conduit fill calculator handles mixed pulls, all seven raceway types and nipples, and shows the areas it used.

Two traps worth knowing

First, three conductors around a bend can wedge when the conduit inner diameter divided by the conductor diameter lands near 3.0. The calculator flags that jam-ratio window. Second, PVC Schedule 80 has a thicker wall than Schedule 40, so the same trade size holds noticeably less. Check the Table 4 columns above before assuming a size that worked in EMT will work in Schedule 80.