NEC Table 250.122 EGC Sizing

Minimum equipment grounding conductor size from NEC Table 250.122, listed by the rating of the overcurrent device protecting the circuit, from 15 A through 2000 A, in copper and aluminum.

NEC Table 250.122, minimum size equipment grounding conductor by the rating of the overcurrent device, 15 A through 2000 A
OCPD rating up toCopperAluminum
15 A14 AWG12 AWG
20 A12 AWG10 AWG
30 A10 AWG8 AWG
40 A10 AWG8 AWG
60 A10 AWG8 AWG
100 A8 AWG6 AWG
200 A6 AWG4 AWG
300 A4 AWG2 AWG
400 A3 AWG1 AWG
500 A2 AWG1/0 AWG
600 A1 AWG2/0 AWG
800 A1/0 AWG3/0 AWG
1000 A2/0 AWG4/0 AWG
1200 A3/0 AWG250 kcmil
1600 A4/0 AWG350 kcmil
2000 A250 kcmil400 kcmil

NEC Table 250.122. Minimum equipment grounding conductor by the rating or setting of the overcurrent device ahead of the circuit. Upsized phase conductors require a proportionally larger EGC · 250.122(B). Parallel runs in separate raceways need a full-size EGC in every raceway · 250.122(F).

How to use this table

Start from the breaker or fuse, not the wire. Find the first row whose rating is at or above your overcurrent device and read the minimum EGC for your material. The EGC is the fault-clearing path that runs with the circuit conductors; its whole job is to carry enough fault current to open that device fast.

When the table row is not enough

If the ungrounded conductors were upsized for any reason, voltage drop being the usual one, the EGC must grow by at least the same ratio of circular-mil areas · 250.122(B). A run sized up two positions for a long feeder drags its EGC up with it, and the table row alone is no longer compliant. For parallel conductors in separate raceways or cables, each raceway gets a full-size EGC sized from this table; the EGC is never split between raceways · 250.122(F).

Related sizing

This table covers equipment grounding. The conductor to the grounding electrode system is sized from the service conductors instead, per Table 250.66. For the circuit conductors the device protects, start from the Table 310.16 ampacity chart or run the free wire size calculator. The JobVolt app's grounding calculator applies the upsizing ratio and the parallel-raceway rule automatically and cites each step.