What Size Ground Wire for a 250 Amp Service or Breaker?

Verified against NEC 2023, checked against the 2026 edition · Last checked August 18, 2026

A 250 amp breaker or feeder needs an equipment grounding conductor of 4 AWG copper or 2 AWG aluminum · Table 250.122. A 250 amp dwelling service is sized differently: its grounding electrode conductor comes from Table 250.66 based on the service conductor size. A rod-only electrode caps it at 6 AWG copper · 250.66(A). Both answers are below.

Common on this rating: commercial feeders and services. Run with 250 kcmil copper circuit conductors, the ground is 4 AWG copper.

Two different tables answer this question. A breaker, circuit or sub panel takes an equipment grounding conductor from Table 250.122, entered with the breaker rating. A service takes a grounding electrode conductor from Table 250.66, entered with the service conductor size. Mixing them up can change the answer by a size or more.

Equipment grounding conductor for a 250 A breaker, circuit or sub panel feeder. Same values in NEC 2023 and 2026.
ConductorSizeBasis
Copper EGC4 AWGTable 250.122
Aluminum EGC2 AWGTable 250.122

The EGC never needs to be larger than the circuit conductors · 250.122(A). Upsized circuit conductors mean a proportionally upsized EGC · 250.122(B). Parallel runs in separate raceways carry a full-size EGC in each raceway · 250.122(F).

Grounding electrode conductor for a 250 A one-family dwelling service, by service conductor size and material. Same values in NEC 2023 and 2026.
Service conductorsGECBasis
Copper service, 4/0 AWG2 AWG Cu or 1/0 AWG AlTable 250.66
Aluminum service, 300 kcmil2 AWG Cu or 1/0 AWG AlTable 250.66
Rod, pipe or plate electrode only6 AWG Cu or 4 AWG Al250.66(A) cap

Service conductor sizes per the 83% rule of 310.12. The rod cap applies when the conductor serves only rod, pipe or plate electrodes; a concrete-encased electrode caps at 4 AWG copper · 250.66(B). Outdoors, aluminum GEC terminations stay 18 inches off the earth · 250.64(A).

Grounding sized in seconds, offline.

The JobVolt app sizes EGC and GEC with the exact table row cited, handles upsizing for voltage drop, and exports inspector-ready PDF submittals.

Download on the App StoreGet it on Google Play

Common questions

What size ground wire for a 250 amp breaker?
An equipment grounding conductor of 4 AWG copper or 2 AWG aluminum, from Table 250.122. The EGC never needs to be larger than the circuit conductors · 250.122(A).
What size ground wire for a 250 amp sub panel?
The same as the breaker answer: 4 AWG copper or 2 AWG aluminum, sized by the 250 A feeder breaker per Table 250.122.
What size ground wire for a 250 amp service?
That is the grounding electrode conductor. For a 250 A one-family dwelling with 4/0 AWG copper service conductors: 2 AWG copper or 1/0 AWG aluminum · Table 250.66. With 300 kcmil aluminum service conductors the row is the same: 2 AWG copper.
Why is the ground to my rod smaller than the table says?
A grounding electrode conductor that runs only to rod, pipe or plate electrodes never needs to be larger than 6 AWG copper or 4 AWG aluminum · 250.66(A). Concrete-encased electrodes cap at 4 AWG copper · 250.66(B).
Is the ground wire the same as the neutral?
No. The grounded service conductor, the neutral, is a current-carrying conductor sized by 250.24(C) and 220.61. It is not the EGC of Table 250.122 and not the GEC of Table 250.66.
What if my circuit conductors were upsized for voltage drop?
If the circuit conductors were upsized for voltage drop, the EGC must be upsized in the same ratio of circular-mil area · 250.122(B).