JobVolt
Table 430.248 · 430.22 · 430.52(C)(1)

How Many Amps Does a 1.5 HP Single-Phase Motor Draw?

Verified against NEC 2023, checked against the 2026 edition · Last checked September 7, 2026

A 1.5 hp single-phase motor draws 20 A at 115 V and 10 A at 230 V, the table currents for 120 V and 240 V systems · Table 430.248. At 230 V its branch-circuit conductors need at least 12.5 A of ampacity, 125% of the table current · 430.22, and the inverse-time breaker tops out at 25 A · Table 430.52(C)(1). Size the wire and the breaker from these table values, not the nameplate · 430.6(A)(1).

Wiring a three-phase motor instead? See 1.5 hp three-phase motor amps.

Table 430.248 full-load current for a 1.5 hp single-phase motor, with the 125% conductor minimum · 430.22 and the maximum inverse-time breaker · Table 430.52(C)(1) at each voltage. The Table 430.248 currents are the same in the 2023 and 2026 editions.
Table voltageSystemFLCConductor min · 430.22Max breaker · 430.52(C)(1)
115 V110 to 120 V20 A25 A50 A
200 V200 V11.5 A14.375 A30 A
208 V208 V11 A13.75 A30 A
230 V220 to 240 V10 A12.5 A25 A

The listed currents are permitted for 110 to 120 V and 220 to 240 V systems · Table 430.248. Wire and breaker are sized from these table values, not the nameplate · 430.6(A)(1). Where 250% of FLC is not a standard rating, the next higher standard rating is shown · 430.52(C)(1)(a).

Maximum branch-circuit short-circuit and ground-fault protection for a 1.5 hp single-phase motor at 230 V, FLC 10 A · Table 430.52(C)(1).
DeviceMax % of FLCComputedStandard size
Inverse-time breaker250%25 A25 A

Where the computed value is not a standard rating in 240.6(A), the next higher standard rating is permitted · 430.52(C)(1)(a). Breaker ratings start at 15 A. Fuse sizes and instantaneous-trip settings are not shown.

Minimum branch-circuit conductor for a 1.5 hp single-phase motor at 230 V: 12.5 A of ampacity, 125% of 10 A · 430.22. THHN-class insulation in raceway, 3 or fewer current-carrying conductors, 86°F ambient.
ConductorSizeAmpacityBasis
Copper · 75°C terminals14 AWG20 ATable 310.16 · 75°C column
Copper · 60°C terminals14 AWG15 ATable 310.16 · 60°C column · 110.14(C)(1)(a)
Aluminum · 75°C terminals12 AWG20 ATable 310.16 · 75°C column

Design B, C or D motors may use the 75°C column · 110.14(C)(1)(a)(4). The small-conductor caps of 240.4(D) do not limit motor branch circuits. Table 240.4(G) sends motor circuit conductors to Article 430, where Part III sets overload and Part IV sets short-circuit and ground-fault protection · 240.4(G). Ground wire from Table 250.122 at the breaker rating. It never needs to be larger than the circuit conductors · 250.122(A).

What changes this answer

  • Table current, not nameplate · 430.6(A)(1)

    Conductor ampacity and the branch-circuit device come from the table value above, not from the nameplate. The nameplate current sizes only the overload protection.

  • Overload protection · 430.32(A)(1)

    Rated or set at no more than 125% of the nameplate amps for a motor with a marked service factor of 1.15 or more or a marked temperature rise of 40°C or less, otherwise 115%. Nameplate, not table.

  • Round-up rule · 430.52(C)(1)(a)

    250% of 10 A lands exactly on 25 A, a standard rating in 240.6(A), so no round-up is needed.

  • Small-conductor caps · 240.4(G)

    The 15, 20 and 30 A caps of 240.4(D) for 14, 12 and 10 AWG copper do not apply here. Motor branch-circuit conductors are governed by Article 430 (Table 240.4(G) lists Parts II through VII), so a 14 AWG copper conductor can sit behind a 25 A breaker on this circuit.

  • Hot locations and shared raceways · 310.15(B)(1), 310.15(C)(1)

    The conductor sizes above assume 86°F and no more than three current-carrying conductors. Ambient above 86°F and four or more conductors in one raceway derate the ampacity. Run the wire size calculator with your conditions.

  • Long runs and voltage drop

    Distance does not change the NEC minimum, but past roughly 100 feet voltage drop usually forces a larger conductor. Motors are sensitive to low voltage at start.

Size the whole motor circuit on the job site, offline.

The JobVolt app runs this same verified math with no signal, adds the overload from the nameplate, keeps every calculation in History, and turns it into an inspector-ready PDF submittal on your letterhead.

Download on the App StoreGet it on Google Play

Common questions

How many amps does a 1.5 hp single-phase motor draw?
20 A at 115 V and 10 A at 230 V, the table currents for 120 V and 240 V systems · Table 430.248. At 208 V the table gives 11 A. The nameplate can differ; wire and breaker are sized from the table · 430.6(A)(1).
What size breaker for a 1.5 hp single-phase motor?
At 230 V, an inverse-time breaker up to 25 A: 250% of 10 A is 25 A · Table 430.52(C)(1), a standard rating in 240.6(A). Overload protection is separate and comes from the nameplate · 430.32(A)(1).
What size wire for a 1.5 hp 230 V single-phase motor?
14 AWG copper with 75°C or 60°C terminations, or 12 AWG aluminum. The conductor needs 12.5 A of ampacity, 125% of the 10 A table current · 430.22, read from Table 310.16.
What is the full-load current of a 1.5 hp single-phase motor at 208 V?
11 A · Table 430.248. At 200 V the table gives 11.5 A. At 208 V the conductors need 13.75 A of ampacity · 430.22 and the inverse-time breaker tops out at 30 A · Table 430.52(C)(1). 250% of 11 A is 27.5 A, rounded up to the next standard rating · 430.52(C)(1)(a).
Do I use the nameplate amps or the table?
The table. Conductor ampacity and the branch-circuit short-circuit and ground-fault device are sized from Table 430.248, not from the nameplate · 430.6(A)(1). The nameplate current sizes only the overload device · 430.32(A)(1).